IMPORTANT SAFEGUARDS
When using electrical equipment, basic safety precautions should always be followed, including the following:
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
1. CAUTION To prevent electrical shock, do not mate unit connector until installation is complete and A.C.
power is supplied to the unit.
2. CAUTION This fixture provides more than one power supply output source. To reduce the risk of electrical
shock, disconnect both normal and emergency sources by turning off the A.C. branch circuit and by discon-
necting the unit connector.
3. CAUTION This is a sealed unit. The integral, high temperature Ni-Cad battery is not replaceable. Replace the
entire unit when necessary and recycle or dispose of the nickel-cadmium battery properly.
4. DO NOT USE OUTDOORS. The I-32 is for use with grounded, UL Listed, indoor fixtures. Not for use in heated
air outlets or hazardous locations.
5. The I-32 requires an unswitched A.C. power source of either 120 or 277 volts. Properly cap the unused A.C.
lead.
6. The I-32 and A.C. ballast must be on the same branch circuit.
7. Do not mount near gas or electric heaters.
8. The I-32 should be mounted in locations and at heights where it will not readily be subjected to tampering by
unauthorized personnel.
9. The I-32 will cold strike and operate one 2 through 4 (20-40W) instant start, rapid start, U shape or circline,
T8 through T12 or 28W T5 fluorescent lamps, including energy saving and long compacts for 90 minutes at
reduced light output.
10. The I-32 is compatible with all A.C. magnetic and electronic ballasts including multiple lamp ballasts with one
lamp operating in the emergency mode.
11. The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.
12. Do not use this equipment for other than intended use.
13. Install in accordance with the National Electrical Code and local regulations.
14. Installation and servicing should be performed by qualified personnel.
15. Lighting fixture manufacturers, electricians, and end-users need to ensure product system compatibility before
final installation.
SAVE THESE INSTRUCTIONS
I-32
TBTS SERIES D
EMERGENCY
LIGHTING EQUIPMENT
INSTRUCTION MANUAL
P.O. BOX 11846 TUCSON, AZ 85734
(520) 294-3292 FAX (520) 741-2837
www.iotaengineering.com
Vue de la page 0
1 2 3 4

Résumé du contenu

Page 1 - INSTRUCTION MANUAL

IMPORTANT SAFEGUARDSWhen using electrical equipment, basic safety precautions should always be followed, including the following:READ AND FOLLOW ALL S

Page 2 - INSTALLATION INSTRUCTIONS

Page 27/8" BUSHINGFIXTUREBALLAST CHANNEL COVERPLASTIC TUBETBTSFIXTURE LENS4. INSTALLING THE THREADED BODY TEST SWITCH (TBTS) Recessed Troffer F

Page 3 - TESTING & MAINTENANCE

Page 35. WIRING THE A.C. INPUTA. The I-32 and A.C. ballast must be on the same branch circuit.B. The I-32 requires an unswitched A.C. power source of

Page 4 - TYPICAL WIRING DIAGRAMS

Page 4TYPICAL WIRING DIAGRAMSFor wiring diagrams of ballasts not shown, consult our Customer Service.Rev. 07151368432-0611. ONE LAMP RAPID START BALL